The fully insulated and fully enclosed ring main unit switchgear is independently developed by Tianrun Company. The high voltage gas insulated switchgear adopts a modular design and can be arranged arbitrarily according to different design schemes, achieving a perfect combination of the common box unit and the expansion unit, meeting the flexible usage requirements of compact switchgear in various secondary transmission and distribution substations.
This GIS gas insulated switchgear is a completely sealed system. All live parts and switches are enclosed in a stainless steel shell, unaffected by the environment. The compact gis switchgear features reliable operation, safety guarantee, compact structure design, small space occupation, maintenance-free, and long service life.
Our high voltage switchgear for sale has passed the type test certification of the national high-voltage electrical appliance test center and is widely used in small secondary distribution stations, box-type switch stations, industrial and mining enterprises, airports, railways, commercial areas, high-rise buildings, expressways, subways, tunnels, and other places with harsh natural conditions.
Features
Excellent Performance
Rationally designed to meet the functional requirements in practical applications.
Reliable power supply to ensure the stable operation of the power distribution system.
Compact structure and small size to save installation space.
Easy to install and operate flexibly, reducing the difficulty of construction and use.
High cost performance, providing superior performance while offering a price advantage.
Advanced Technical Concepts
Adhering to the design concepts of green and environmental protection in terms of ideas and concepts,gas insulated switchgear meets the current demand for environmentally friendly products.
Parameters
The Main Technical Parameters
Items Unit Circuit-breaker unit Load switch unit
Rating voltage kV 12
Rating frequency Hz 50
Rating capacity kA 630
1Min power frequency withstand voltage
To the ground/interphase kV 42
Fracture 48
Lightning impulse withstand voltage To the Ground/Interphase kV 75
Fracture 85
Rating short-time withstand current and duration Main circuit kA 20/4S
Ground circuit 17.4/2S
Rating Peak withstand current Main circuit kA 50
Ground circuit 43.5
Rating short circuit current(peak) kA 50
Rating short circuit breaking current kA 20 /
Rating short circuit breaking current times Times 30 /
Rating operation sequence 0-0.3S-CO-
180S-CO
Rating cable/line charging breaking test kA C2level /
Interphase ground fault breaking current 17.4 /
Rating active loans breaking current A / 630
Rating closed loop breaking current A / 630
Rated cable Charing breaking test A / 10
5%Rated active load breaking current A / 31.5
Grounding switch close times Times 5
loop resistance uΩ ≤140
Rated gas pressure(20℃Presure) MPa 0.02
Mechanical life Vacuum switch Times 10000
Isolator 3000
Earthing switch 3000
Protection level Enclose IP4X
Gas box IP67
Operational power supply V AC220/DC220/DC110/
DC48/DC24
Rated annual leakage rate % ≤0.1
Cabinet Size(single circuit) mm 420×822x1420
Tolerance to internal arc fault kA/s 20/0.5
Moisture content in dry air ppm ≤150
Benefits
Wide Applicability
Gas insulated switchgear is suitable for three-phase AC 50Hz, 12KV rated voltage distribution systems and can be applied in various places such as smart grids, urban distribution, building complexes, industrial enterprises, and other load centers' distribution stations and box-type switchgear stations.
Adapting to Market Trends
As switchgear with little or no SF6, gas insulated switchgear conforms to the future technological development direction and has a promising market prospect.
Use
Normal use conditions
Ambient air temperature: upper limit +40℃, lower limit -40℃
Humidity: the daily average value of relative humidity shall not exceed 95%; the monthly average value shall not exceed 90%
Water vapor pressure: the daily average value shall not exceed 2.2 kPa; the monthly average value shall not exceed 1.8 kPa
Altitude not exceeding 2000m.
The ambient air is not obviously contaminated by dust, smoke, corrosive and flammable gases, vapors, or salt fog.
The amplitude of electromagnetic interference induced in the secondary system does not exceed 1.6 kV.
There are many gas insulated switchgear manufacturers, but we are one of the best choices for you.
As a trustworthy and reliable power transmission manufacturers, we provide you with electric power distribution equipment.